机组型号
|
风量
|
余压
|
四排冷量
|
六排冷量
|
热水加热量
|
蒸汽加热量
|
再生电加热量
|
电极加湿量
|
电机功率
|
TZK
|
CMH
|
Pa
|
kw
|
kw
|
kw(2排)
|
Kw(单排)
|
kw
|
kg/h
|
kw
|
HM030
|
3000
|
500
|
10.4
|
13.4
|
20
|
39
|
9
|
4
|
1.5
|
HM040
|
4000
|
500
|
14.8
|
16.9
|
26
|
52
|
12
|
5
|
2.2
|
HM050
|
5000
|
500
|
18
|
23.6
|
33
|
65
|
15
|
10
|
2.2
|
HM060
|
6000
|
500
|
20.7
|
27
|
40
|
78
|
18
|
10
|
3
|
HM080
|
8000
|
500
|
28.2
|
33.7
|
52
|
104
|
24
|
13
|
4
|
HM100
|
10000
|
600
|
39.1
|
45.6
|
65
|
130
|
30
|
13
|
5.5
|
HM120
|
12000
|
600
|
44.6
|
54.8
|
80
|
156
|
36
|
15
|
5.5
|
HM150
|
15000
|
600
|
58.2
|
63.4
|
98
|
195
|
45
|
15
|
7.5
|
HM180
|
18000
|
600
|
66.4
|
76.6
|
120
|
234
|
54
|
25
|
11
|
HM200
|
20000
|
700
|
79.1
|
95.7
|
130
|
260
|
60
|
30
|
11
|
HM230
|
23000
|
700
|
88.4
|
113.9
|
150
|
300
|
60
|
30
|
11
|
HM250
|
25000
|
700
|
96.3
|
116.9
|
163
|
325
|
72
|
45
|
15
|
HM280
|
28000
|
700
|
104.9
|
127.6
|
182
|
364
|
72
|
45
|
15
|
HM300
|
30000
|
700
|
108.9
|
137
|
195
|
390
|
75
|
45
|
15
|
HM350
|
35000
|
800
|
131.9
|
164
|
225
|
450
|
90
|
60
|
18.5
|
HM400
|
40000
|
800
|
153.3
|
174
|
260
|
520
|
100
|
60
|
22
|
HM450
|
45000
|
800
|
160.4
|
205.7
|
290
|
580
|
108
|
60
|
30
|
HM500
|
50000
|
800
|
178.4
|
234
|
325
|
650
|
120
|
75
|
30
|
HM550
|
55000
|
800
|
196.2
|
257.4
|
355
|
715
|
134
|
75
|
30
|
HM600
|
60000
|
800
|
214.1
|
280.8
|
390
|
780
|
144
|
90
|
37
|
-
注:
1、制冷名义工况:进风干球28℃,进风湿球18℃,进水温度12℃,供回水温差为5℃。
2、制热名义工况:进风干球15℃,进水温度60℃,出水温度50℃。